Shell Diala S4 ZX-I (Dầu Cách Điện)-Electrical Insulating oil

Được viết bởi
Đánh giá bài viết
(8 Đánh giá)

#Shell Diala S4 ZX-I (Dầu Cách Điện Shell) is the new electrical insulating oil from Shell designed to meet the challenges presented by the latest power transformers.

 

#Diala S4 ZX-I - #Electrical Insulating oil (Dầu cách điện) is the new electrical insulating oil from Shell designed to meet the challenges presented by the latest power transformers. It offers an extended oil life with the peace of mind of zero sulphur content.
#Shell Diala S4 ZX-I is manufactured from zero sulphur base oils produced using Shell’s GTL (gas-to-liquid) technology.


These base oils offer a high degree of compositional consistency and have an excellent response to anti-oxidant. In addition they are globally available and free from PCBs, DBDS and passivators.


Shell Diala S4 ZX-I (Electrical Insulating oil) meets both the established and new industry copper corrosion tests.

 

Diala S4 ZX-I là thế hệ dầu cách điện mới của Shell, đáp ứng thách thức của những máy biến thế mới nhất. Dầu có tuổi thọ kéo dài và giúp người dùng yên tâm sử dụng do không chứa lưu huỳnh.

Shell Diala S4 ZX-I sử dụng dầu gốc không chứa lưu huỳnh được điều chế theo công nghệ GTL (khí hóa lỏng) của Shell. Các thành phần trong dầu gốc có độ ổn định rất cao và khả năng chống ôxy hóa tuyệt vời. Ngoài ra, loại dầu gốc này có mặt trên toàn cầu, không chứa các chất PCB, DBDS và chất thụ động hóa bề mặt.

Shell Diala S4 ZX-I đáp ứng cả các thử nghiệm chống ăn mòn đồng công nghiệp trước đây và hiện nay.

An Phát VN - Nhà phân phối dầu cách điện Shell Diala S4 ZX-I tin cậy

 

DESIGENED TO MEET CHALLENGES

Performance, Features & Benefits

 * Extended oil life ·
Shell Diala S4 ZX-I is a fully inhibited oil giving outstanding oxidation performance and an extended oil life. Shell Diala S4
ZX-I is also suitable for use in highly loaded applications.

 * Transformer protection ·
Shell Diala S4 ZX-I is manufactured from a zero sulphur* base oil, making it intrinsically non-corrosive towards copper, without the need for passivation or other additives.
Shell Diala S4 ZX-I meets all relevant tests for copper corrosion, namely the established DIN 51353 (Silver Strip Test), ASTM D1275, and also the latest more severe tests: IEC 62535 and ASTM D1275B.
*Sulphur content below 1ppm detection limit of ASTM D5185

 

System efficiency ·
The good low temperature viscometric properties of the oil ensure proper heat transfer inside the transformer, even from very low starting temperatures.


Shell Diala S4 ZX-I is specially dried and handled to achieve a low water content and retain a high breakdown voltage at point of delivery. This enables it to be used in many applications without further treatment.

 

Main Applications
Specifications, Approvals & Recommendations IEC 60296 (2012): Table 2 Transformer Oil (I) (Inhibited Oil) Section 7.1 ("Higher oxidation stability and low sulphur content").
·
For a full listing of equipment approvals and recommendations, please consult your local Shell Technical Help Desk.

 

Health, Safety & Environment

Health and Safety ·
Shell Diala S4 ZX-I is unlikely to present any significant health or safety hazard when properly used in the recommended application and good standards of personal hygiene are maintained.

Shell Diala S4 ZX-I is free from polychlorinated biphenyls (PCB).

Avoid contact with skin. Use impervious gloves with used oil. After skin contact, wash immediately with soap and water.
Guidance on Health and Safety is available on the appropriate Material Safety Data Sheet, which can be obtained from your Shell representative.

 

Protect the Environment
Take used oil to an authorised collection point. Do not discharge into drains, soil or water.

 

Additional Information

Storage precautions
The critical electrical properties of Shell Diala are easily compromised by trace contamination with foreign material. Typically encountered contaminants include moisture, particles, fibres and surfactants. Therefore, it is imperative that electrical nsulating oils be kept clean and dry.
It is strongly recommended that storage containers be dedicated for electrical service and include air-tight seals. It is further recommended that electrical insulating oils are stored indoors in climate-controlled environments.

 

Advice
Advice on applications not covered here may be obtained from your shell representative

-------------------------------------

REGULATORY INFORMATION
Safety, health and environmental regulations/legislation specific for the substance or mixture Standard for the Uniform Scheduling of Medicines and Poisons : No poison schedule number allocated

Product classified as per Work Health Safety Regulations – Implementation of the Globally Harmonized System of Classification and Labelling of Chemicals (GHS) 2012 and SDS prepared as per national model code of practice for preparation of safety data sheet for Hazardous chemicals 2011 based on Globally Harmonized Classification version 3.
National Model Code of Practice for the Labelling of Workplace Hazardous Chemicals (2011).
Australian Code for the Transport of Dangerous Goods by Road and Rail (ADG code). Standard for the Uniform Scheduling of Medicines and Poisons (SUSMP).
The regulatory information is not intended to be comprehensive. Other regulations may apply to this material.

 

Other international regulations
The components of this product are reported in the following inventories:

EINECS : All components listed or polymer exempt.
TSCA : All components listed.
AICS : All components listed.

 

OTHER INFORMATION
Full text of H-Statements
H304 : May be fatal if swallowed and enters airways
H400 : Very toxic to aquatic life.
H410 : Very toxic to aquatic life with long lasting effects.

Full text of other abbreviations
Aquatic Acute : Acute aquatic toxicity
Aquatic Chronic : Chronic aquatic toxicity
Asp. : Tox. Aspiration hazard

 

Engineering measures:
The level of protection and types of controls necessary will vary depending upon potential exposure conditions. Select controls based on a risk assessment of local circumstances.


Appropriate measures include:
Adequate ventilation to control airborne concentrations.
Where material is heated, sprayed or mist formed, there is greater potential for airborne concentrations to be generated.


General Information:
Define procedures for safe handling and maintenance of controls.
Educate and train workers in the hazards and control measures relevant to normal activities associated with this product.
Ensure appropriate selection, testing and maintenance of equipment used to control exposure, e.g. personal protective equipment, local exhaust ventilation.


Drain down system prior to equipment break-in or maintenance.
Retain drain downs in sealed storage pending disposal or subsequent recycle.
Always observe good personal hygiene measures, such as washing hands after handling the material and before eating, drinking, and/or smoking. Routinely wash work clothing and protective equipment to remove contaminants. Discard contaminated clothing and footwear that cannot be cleaned.

 

Engineering measures:
The level of protection and types of controls necessary will vary depending upon potential exposure conditions. Select controls based on a risk assessment of local circumstances.


Appropriate measures include:
Adequate ventilation to control airborne concentrations.
Where material is heated, sprayed or mist formed, there is greater potential for airborne concentrations to be generated.


General Information:
Define procedures for safe handling and maintenance of controls.
Educate and train workers in the hazards and control measures relevant to normal activities associated with this product.
Ensure appropriate selection, testing and maintenance of equipment used to control exposure, e.g. personal protective equipment, local exhaust ventilation.
Drain down system prior to equipment break-in or maintenance.
Retain drain downs in sealed storage pending disposal or subsequent recycle.
Always observe good personal hygiene measures, such as washing hands after handling the material and before eating, drinking, and/or smoking. Routinely wash work clothing and protective equipment to remove contaminants. Discard contaminated clothing and footwear that cannot be cleaned.
Practice good housekeeping.


Practice good housekeeping.

 

AICS - Australian Inventory of Chemical Substances; ANTT - National Agency for Transport by Land of Brazil; ASTM - American Society for the Testing of Materials; bw - Body weight; CMR - Carcinogen, Mutagen or Reproductive Toxicant; CPR - Controlled Products Regulations; DIN - Standard of the German Institute for Standardisation; DSL - Domestic Substances List (Canada); ECx - Concentration associated with x% response; ELx - Loading rate associated with x% response; EmS - Emergency Schedule; ENCS - Existing and New Chemical Substances (Japan); ErCx - Concentration associated with x% growth rate response; ERG - Emergency Response Guide; GHS - Globally Harmonized System; GLP - Good Laboratory Practice; IARC - International Agency for Research on Cancer; IATA - International Air Transport Association; IBC - International Code for the Construction and Equipment of Ships carrying Dangerous Chemicals in Bulk; IC50 - Half maximal inhibitory concentration; ICAO - International Civil Aviation Organization; IECSC - Inventory of Existing Chemical Substances in China; IMDG - International Maritime Dangerous Goods; IMO - International Maritime Organization; ISHL - Industrial Safety and Health Law (Japan); ISO - International Organisation for Standardization; KECI - Korea
Existing Chemicals Inventory; LC50 - Lethal Concentration to 50 % of a test population; LD50 - Lethal Dose to 50% of a test population (Median Lethal Dose); MARPOL - International Convention for the Prevention of Pollution from Ships; n.o.s. - Not Otherwise Specified; Nch - Chilean Norm; NO(A)EC - No Observed (Adverse) Effect Concentration; NO(A)EL - No Observed (Adverse) Effect Level; NOELR - No Observable Effect Loading Rate; NOM - Official Mexican Norm; NTP - National Toxicology Program; NZIoC - New Zealand Inventory of Chemicals; OECD - Organization for Economic Co-operation and Development; OPPTS - Office of Chemical Safety and Pollution Prevention; PBT - Persistent, Bioaccumulative and Toxic substance; PICCS - Philippines Inventory of Chemicals and Chemical Substances; (Q)SAR - (Quantitative) Structure Activity Relationship; REACH - Regulation (EC) No 1907/2006 of the European Parliament and of the Council concerning the Registration, Evaluation, Authorisation and Restriction of Chemicals; SADT - Self-Accelerating Decomposition Temperature; SDS - Safety Data Sheet; TCSI - Taiwan Chemical Substance Inventory; TDG - Transportation of Dangerous Goods; TSCA - Toxic Substances Control Act (United States); UN - United Nations; UNRTDG - United Nations
Recommendations on the Transport of Dangerous Goods; vPvB - Very Persistent and Very Bioaccumulative; WHMIS - Workplace Hazardous Materials Information System


 

Nguồn : Shell.com

Dầu Cách Điện Shell - An Phát VN

Được xem 1007 lần

Liên hệ với chúng tôi để biết thêm thông tin

Các thông tin (*) yêu cầu phải nhập. Mã cho phép dùng các thẻ HTML.

Công ty TNHH An Phát VN

Liên hệ với An Phát VN qua di động: 0916.744.366 hoặc gửi email tới địa chỉ kd.anphatvn@gmail.com . Chúng tôi chuyên cung cấp dịch vu xây dựng công nghiệp và dân dụng, chống thấm các công trình xây dựng, thủy lợi, cấp thoát nước, lắp đặt hệ thống điện nhẹ, điện nước, Internet... Đại lý phân phối bán sĩ và lẻ dầu nhớt Shell trong công nghiệp & vận tải.

https://anphatvn.com